Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Circle K #30224 <br /> Tank #: 2 Test Date: 5/18/97 <br /> Product: Unleaded Premium Work#: 2201416 <br /> Test Method: Vacutect Test Method: TLDT <br /> Capacity: 9816 Manufacturer: Red Jacket <br /> Diameter(in): 92 L/D Model: PLD <br /> Product Level(in): 19 L/D Serial#: 30790-1303 <br /> Liquid Volume(Gals): 1409 Line Drain Back(ml): 380 <br /> Liquid Percent(%): 14.4% L/D Trip Time(sec): 1 <br /> Specific Gravity: 0.750 Holding Pressure(psi): 14 <br /> Coef.of Expansion: 0.000655 Metering Pressure(psi): 10 <br /> Water On Tank(in): 55 L/D Test Rate(gph): 3.0 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): <br /> Head Pressure(psi): -1.5 <br /> Test Start Time: 9:11 PM <br /> Test End Time: 10:48 PM Test Method: TLD-1 <br /> Test Rate(gph): Pump Brand: Red Jacket <br /> Test Result: PASS System Type: Pressure <br /> Line Pressure(psi): 50 <br /> Line Start Time: 10:09 PM <br /> Line End Time: 10:39 PM <br /> Test Method: ULLAGE <br /> UllageVolume(gals.): 8407 Line Start Level: 50 <br /> Line End Level: 50 _ <br /> Ullage Test Time: 9:11 PM <br /> Ullage Vacuum(psi): 2.3 Line Test Rate(gph): 0.000 <br /> Line Test Result: PASS <br /> Ullage Result: PASS <br /> 3 <br />