Laserfiche WebLink
TANK ANNULAR TESTING <br /> :.:..:.:.... <br /> Ts $ .lof . �! Mattufactuccc E;:lndustiy fitandand �3 Prafeasiona(Engr f7 Qthec(see below) <br /> Test M tF10E� 5 .5:. ._. C3 Pressure.. i Yaeuuen 4 .HydrostaH Q Other(see ielow) <br /> Mec�S[Il'lliC Eq��pment Uset 'acuutm Gauge {ranged to 3o ineTtes tig� <br /> . . <br /> . <br /> QesG�E Ivan. :::::::: flank# Tank#2 Tank:#3 <br /> Tank Manufacturer XerxesXerxes Xerxes <br /> Tank Type FRP FRP FRP <br /> 8000Tank Capacity 0,000 <br /> Product Stored Gasoline-87 Gasoline-89 Gasoline-91 <br /> Is this a multi-compartment tank? No No No <br /> Brine filled or Dry Annular? Dry Dry Dry <br /> (if brine filled,perform no vacuum testing) <br /> Monitoring system show normal annular? Yes Yes Yes <br /> Is water table above tank bottom? Unknown Unknown Unknown <br /> Was sensor removed for testing? Yes Yes Yes <br /> >:Was sensor properly replaced after testing? Yes Yes Yes <br /> Wait time for vacuum to stabilize hr:min 0:20 0:12 0:19 <br /> Test start time 9:02 AM «: 8:50 AM 9:03 AM <br /> Initial vacuuminches H 10 10 <br /> ( 9) 10 <br /> Test end time 10:02 AM 9:50 AM 10:03 AM <br /> Final vacuum inches H 10 10 <br /> ( g) 10 <br /> «< Test duration ) <br /> hours:minutes 1:00 1:00 1:00 <br /> ( <br /> Change in vacuum(inches Hg) 0 0 0 <br /> Pass/Fail threshold )/hour inches H 2 2 2 <br /> ( Hg/hour) <br /> TEST RESULT PASS PASS PASS <br /> Comments: <br /> 0 2002 Walton Engineering,Inc. <br />