~ <br /> &4RY PETERS EN"jrERpP,' SES <br /> 113WN COLOMA RD . B-7 <br /> RANCHO CORDOVA , CA , �5,-,70 <br /> 916-638-7198 <br /> oate : 6-19-88 <br /> Ref . #: 880619GP <br /> To : DAVE CASTRO <br /> U.C.L .L.N.L . <br /> P.O.BOX 808 L-193 <br /> LIVERMORE <br /> Test iocation : TANK #879-G1U1 & 879-G2U1 , SITE 300 . <br /> On 6-19-88 testing was completed , using the Tank Audit LEAK <br /> COMPUTER in accordance with the precision test requirements of <br /> WFPA 329-1983 and Section 2643 of the California Underground Tank <br /> Regulations (Aug . 1985) . The criter. a for +an� <br /> integrity allowed by these documents ! s based opor � de �ec � / o� <br /> limit of 8 .05 gal/hr and a consideration of other variable <br /> factors . <br /> } eak tank+ <br /> Tank gals . contents level rat* tank pIpes <br /> 879-G1U1 10000 REGULAR * 33" - . 03 FIA-SS PASS <br /> 879-G2U1 10000 UNLEADED * 33" 0 . 02 PAS- PASS <br /> ( GPH) <br /> *LEVEL IN FILL PIPE, ABOVE TANK TOP. <br /> A copy of the data is attached. <br /> Sincerely <br /> GARY P ERS ENT. <br />