Laserfiche WebLink
1988 PRECISION TANK TEST RESULTS <br /> LAWRENCE LIVERMORE NATIONAL LABORATORY - SITE 300 <br /> Capacity Test Results Test Test <br /> Tank (Gallons) Contents (Gal Hr) Date Method* Comments <br /> 805-41D 300 Diesel +0.018 5-26-88 H-S <br /> 827-11D 280 Diesel 0.00 6-09-88 LC-S <br /> 827-12D 8000 Diesel 0.01 6-09-88 LC-S <br /> 834-11D 1000 Diesel -0.01 6-02-88 LC-S <br /> 836-41D 280 Diesel 0.00 6-14-88 LC-S <br /> 865-11D 4000 Diesel 0.00 5-19-88 LC-S <br /> 871-11D 2000 Diesel -0.038 5-12-88 H-S <br /> *874-11D 5000 Diesel N/A 4-13-88 Helium See below <br /> 875-11D 3000 Diesel 0.00 5-12-88 H-S <br /> 877-11D 2000 Diesel -0.022 5-26-88 H-S <br /> 879-GlU1 10000 Regular -0.03 6-19-88 LC-S <br /> 879-G2U1 10000 No-Lead 0.02 6-19-88 LC-S <br /> *874-11D - Results indicate pipe leak - Tank no longer in service <br /> * H-S — Horner "EZY-CHEK" - Full System Test <br /> LC-S — Tank Audit LEAK COMPUTER - Full System Test <br />