The average product temperature is measured during the test/ <br /> data recording period by a specially constructed sensing coil . <br /> Therefore, recorded volume changes are adjusted or compensated <br /> for any expansion or contraction of fuel volume due to tempera- <br /> ture changes . Product volume changes versus temperature are <br /> calculated, using coefficient of expansion determined from table <br /> of temperature/density. If the tank is leaking at a detectable <br /> rate, the actual fluid volume, recorded volume corrected for <br /> volume changes due to possible temperature change , will show a <br /> net loss of 0.05/gallon or greater per hour of test period . The <br /> changes in volume are reflected in level and are instantly <br /> recorded. <br /> 4.0 Equipment Description <br /> Descriptions of the two tank test equipment/systems are sum- <br /> marized below: <br /> 4.1 PETRO TITE <br /> The equipment/system can be described in three essential <br /> functional components : <br /> - the product circulating probe and pump; <br /> - temperature sensor and meter; and <br /> - the standpipe-graduate cylinder parts. <br /> The product circulation probe is connected to a 25 gpm pump, <br /> positioned above grade. The probe has an inflatable bladder that <br /> makes a liquid/product seal with the inside of the fillpipe. The <br /> -3- <br />