09/22/05 11:03 FAX 925 422 2748 EPD / WGNG 9003 <br /> SWRCB,January 2002 FINAL DRAFT Page 2 of 7 <br /> - 4. TANK ANNULAR TESTING <br /> Test Method Developed By: 0 Tank Manufacturer Industry Standard ❑Professional Engineer <br /> El Other(Specify) <br /> Test Method Used: ❑Pressure Vacuum ❑Hydrostatic <br /> ❑ Other(Specify) <br /> Test Equipment Used: 0 to 30"hg Dial Gauge with I lb increments. Equipment Resolution: 2%@ Mid <br /> Tank# Tank# Tank# Tank# <br /> 882-DIU2 <br /> Is Tank Exempt From Testing?' []Yes ®No [:]Yes E]No E]Yes E]No F]Yes <br /> Tank Capacity: 1500g <br /> Tank Material: Steel/Fiberglass <br /> Tank Maritifticturer: Modem Welding <br /> Product Stored: Diesel <br /> Wait time between applying <br /> pressure/vacuum/water and 10 minutes <br /> starting test: <br /> Test Start Time., 8:22am <br /> Initial Reading(Pq): 10.00"hg <br /> Test End Time: 9:22am <br /> Final Reading(RF): 10.00"hg <br /> Test Duration: 60 minutes <br /> Change in Reading(RF-R�: 0.00"hg <br /> Pass/Fail Threshold or Criteria: 0.00"hg <br /> 777�[ P�7 <br /> ass <br /> Was sensor removed for testing? ®Yes E]NoE]NA []YesE]NoE]NA E]Yes E]No E]NA [3Yes L7,No F]NA <br /> Was sensor properly replaced and ®yes E]No DNA [1YesE1No EINA E]Yes E]NoE]NA E]Yes ONo EINA <br /> verified functional after testing? I -- <br /> Comments—(Include information on repairs made prior to testing,and recommended follow-up for failed tests.) <br /> This is an Emergency Generator Tank. <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and seta idary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. (California Code of Regulations,Title 23,Section 2637(a)(6)) <br />