t <br /> AFFILIATE <br /> Thornton Environmental Construction Inc. PCI, <br /> P.O. Box 360833 Milpitas, CA 95036-0833 <br /> Phone (408) 946-1015 9 (209) 834-0792 • Fax(209) 834-0795 <br /> ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br /> Name: Lawrence Livermore National Laboratory Date: 9-14-2006 <br /> Address: Site 300, Tracy, CA 95376 Bldg: 882 <br /> Test Method Developed By: ❑ Spill Bucket Manufacturer ❑x Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: © Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Caldwell Systems Sump Level Change Indicator <br /> Equipment Resolution: 0.0025" <br /> Spill Box# Spill Box# Spill Box# Spill Box# <br /> 882-D1U] <br /> Nominal Bucket Capacity in �Gallons <br /> gallons: <br /> Test fails if the bucket does pass <br /> not hold at least 5 allons <br /> Bucket Depth(inside 15" <br /> measurement): <br /> Wait time between filling with 5 Minutes <br /> water and starting test: <br /> Test Start Time: 9:50a <br /> Initial Reading(RI): 14.50" <br /> Test End Time: 10:06a <br /> Final Reading(RF): 14.50" <br /> Test Duration: 16 Minutes <br /> Change in Reading(RF-RI): 0.00" <br /> Pass/Fad Threshold/Criteria: 0.00" <br /> Test Result: tlil Pass t]Fail ❑Pass ❑Fail ❑Pass ❑Fail ❑Pass L3 Fail <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Test water was disposed of by LLNL. <br /> Technician Name: Brian Thornton Signature: - /-\_ <br />