Laserfiche WebLink
f <br />AFFILIATE <br />Thornton Environmental Construction,, Inc. T j <br />P.O. Box 360833 Milpitas, CA 95036-0833 <br />Phone (408) 946-1015 9 (209) 834-0792 • Fax (209) 834-0795 <br />ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br />Name: Lawrence Livermore National Laboratory Date: 8-30-2010 <br />Address: Site 300, Tracy, CA 95376 Bldg: 882 <br />Test Method Developed By: ❑ Spill Bucket Manufacturer ®Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: 1] Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Caldwell Systems Sump Level Change Indicator Ei ment Resolution: 0.0025" <br />Spill Bog # Spill Bog # Spill Box # Spill Box # <br />882-DlU1 <br />Nominal Bucket Capacity in 7.5 Gallons <br />gallons: <br />Test fails if the bucket does Pass <br />not hold at least 5 gallons <br />Bucket Depth (inside 15" <br />measurement): <br />Wait time between filling with 5 minutes <br />water and starting test: <br />Test Start Time: 9:48a <br />Initial Reading (RI): 14.375" <br />Test End Time: 10:48a <br />Final Reading (RF): 14.25' <br />Test Duration: 60 minutes <br />Change in Reading (RF -RI): -0.063GPH <br />Pass/Fail Threshold / Criteria: O. IOGPH <br />Test Result: lel Pass ❑ Fail <br />0 Pass 0 Fail <br />0 Pass ❑ Fail <br />❑ Pass 17 Fail <br />Comments —(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Drain valve was removed and cleaned, then reinstalled in order to pass. <br />Test water was disposed of by LLNL. <br />A leak rate of less than 0.1OGPH was calculated, and spill containment passed. <br />Technician Name: Brian Thornton <br />