Laserfiche WebLink
AFFILIATE <br />' Construction,, Inc. PCI <br />IL Thornton Environmental Co str , <br />P.O. Box 360833 Milpitas, CA 95036-0833 <br />Phone (408) 946-1015 • (209) 834-0792 • Fax (209) 834-0795 <br />ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br />Name: Lawrence Livermore National Laboratory Date: 9-19-2008 <br />Address: Site 300, Tracy, CA 95376 Bldg: 879 <br />Test Method Developed By: ❑ Spill Bucket Manufacturer x❑Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: © Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Visual test <br />Equipment Resolution: 0.0625" <br />Spill Box # Spill Box # Spill Box # Spill Box # <br />879-G3U1 <br />Nominal Bucket Capacity in 5 Gallons <br />eallons_ <br />Test fails if the bucket does <br />Pass <br />not hold at least 5 gallons <br />5 Minutes <br />Bucket Depth (inside <br />measurement): <br />12.5" <br />Wait time between filling with <br />water and starting test: <br />5 Minutes <br />Test Start Time: <br />10:15a <br />Initial Reading (Rl): <br />11.4375" <br />Test End Time: <br />11:15 <br />Final Reading (RF): _ <br />11.4375" <br />Test Duration: <br />2 -Minutes <br />Change in Reading (RF -RI): <br />0.00" <br />Pass/Fail Threshold / Criteria: <br />0.00" <br />Test Result- <br />0 Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Ll Pass D Fail <br />❑ Pass ❑ Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />This report reflects a retest of 879-G3U1 spill bucket after replacement of the fill cap. <br />Test water was disposed of by LLNL. <br />Technician Name: Brian Thornton Signature: <br />