Laserfiche WebLink
N <br />SWRCB. January 2002 FINAL DRAFT Page 3 of 7 <br />A QIWCnNn A RV PIPR TRqTTNG <br />Test Method Developed By: Piping Manufacturer Industry Standard Professional Engineer <br />El other (specify) <br />Test Method Used: N Pressure El vacuum El Hydrostatic <br />E] Other (Specify) <br />—1 <br />Test Equipment Used.- <br />Test gRu Used: 0 to l5psi Dial GaMe with 1/2 lb increments <br />Equipment resolution: <br />2% A Mid Scale_ <br />_�ipLnent <br />Piping Run # <br />882-DIU2 FOS/FOR <br />Piping Run # <br />Piping Run <br />Piping Run # <br />Piping Material: <br />FRP <br />Piping Manufacturer: <br />Ameron <br />Piping Diameter: <br />41, <br />Length of Piping Run: <br />12' <br />Product Stored: <br />Diesel <br />Method and location of <br />piping -run isolation: <br />Boot (dSump. <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 minutes <br />Test Start Time: <br />9:30am <br />Initial Reading (RI): <br />5.00psi <br />Test End Time: <br />10:30am <br />Final Reading (RF): <br />5.00psi <br />Test Duration: <br />60 minutes <br />Change in Reading (RF- I): <br />0.00psi <br />Pass/Fail Threshold or <br />Criteria: <br />0.00psi <br />Test Result <br />Opan E]Fail <br />OPm OFail <br />OPass 1r it <br />F] ass E]Fail <br />Comments — (Include infonnation on repairs made prior to testing, and recommendedfollow-upforfailed tests.) <br />4" Ameron FRP piping over common Steel FOR and FOS piping, <br />Test boot was pulled back after testing was complete. <br />