SWRCB. January 2002 <br />FINAL DRAFT <br />5. SECOVDLWf-PHW-TL—�,'VG <br />Test Method Developed By: [] Piping Manufacturer ED Industry Standard Professional Engineer <br />El Other (Specify <br />Test Method Used: 0 Pressure El Vacuum El Hydrostatic <br />[I Other (Specify) <br />Test Equipment Used: 0 to 15psi Dial Gauge Equipment Resolution: 2% La,) Mid Scale <br />Piping Run # <br />879-G3U1 <br />Piping Run # <br />879-DIUI <br />Piping Run # <br />Piping Run # <br />Piping Material-. <br />FRP <br />Single Wall Steel <br />Piping Manufacturer: <br />Ameron <br />NA <br />Piping Diameter: <br />3" <br />2" <br />Length of Piping Run: <br />46' <br />21' <br />Prodi ct Stored: <br />Unleaded <br />Diesel <br />Method and location of <br />_pipmg-run isolation: <br />Boot (aD Sump <br />NA <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 minutes <br />NA <br />Test Start Time: <br />11:30am <br />NA <br />Initial Reading (RI): <br />4.75psi <br />NA <br />Test End Time: <br />12:35pm <br />NA <br />Final Reading (RF): <br />4.75psi <br />NA <br />Test Duration: <br />65 minutes <br />NA <br />Change in Reading (RF -R,): <br />0.00psi <br />NA <br />Pas ail Threshold or <br />Criteria: <br />0.00psi <br />NA <br />Test Result <br />NPASS OFail <br />ElPass OFail <br />[]Pass OFA <br />OPass []Fail <br />Comments — (Include infonnation on repairs made prior to testing, and recommendedfollow-upforfailed tests.) <br />Diesel product piping is safe suction, and was verified on this visit. <br />