Laserfiche WebLink
AFFILIATE <br /> %-Lw Thornton Environmental Construction Inc. TTI <br /> P.O. Box 360833 Milpitas, CA 95036-0833 <br /> Phone(408)946-1015 •(209)834-0792 • Fax(209) 834-0795 <br /> ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br /> Name: Lawrence Livermore National Laboratory Date: 8-02-2011 <br /> Address: Site 300, Tracy, CA 95376 Bldg: 882 <br /> Test Method Developed By: ❑Spill Bucket Manufacturer ®Industry Standard 0 Professional Engineer <br /> ❑Other(SpeC1ff) <br /> Test Method Used: ®Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Caldwell Systems Sump Level Change Indicator uiment Resolution: 0.0025" <br /> Spill Boz# Spill Boz# Spill Boz# Spill Bog# <br /> 882-D1U1 <br /> Nominal Bucket Capacity in 7.5 Gallons <br /> gallons: <br /> Test fails if the bucket does Pass <br /> not hold at least 5 gallons <br /> Bucket Depth(inside 15" <br /> measurement): <br /> Wait time between filling with 5 minutes <br /> water and starting test: <br /> Test Start Time: 9:45a <br /> Initial Reading(Ril: 14.25" <br /> Test End Time: 10:35a <br /> Final Reading(RF): 14.25" <br /> Test Duration: 50 minutes <br /> Change in Reading(RF-R1): O.00GPH <br /> Pass/Fad Threshold/Criteria: O.10GPH <br /> Test Result: ®Pass ❑Fail ©Pass E3 Fail Ll Pass D Fail Q Pass ❑Fail <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Test water was disposed of by LLNL. <br /> Technician Name: Brian Thornton Signature: /S <br />