Laserfiche WebLink
SWRCB. January 2002 ALD Page 3 of 7 <br />Test Method Developed By: Piping Manufacturer Industry Standard 0 Professional Engineer <br />El Other (Specyy) <br />Test Method Used: El Pressure 0 Vacuum El Hydrostatic <br />El Other (Specify) <br />Test Equipment Used: 0 to -30" lig Dial Gauge <br />Equipment Resolution: 2% Oa, Mid Scale <br />Piping Run # <br />879-TFUGOI <br />Piping Run # <br />879- 01 <br />Piping Run # <br />Piping Run # <br />Piping Material: <br />FRP <br />Single Wall Steel <br />Si <br />Piping Manufacturer: <br />Ameros <br />NA <br />Piping Diameter: <br />Y <br />2" <br />Length of Piping Run: <br />46' <br />21' <br />Product Stored: <br />Unleaded <br />Diesel <br />Method and location of <br />piping-ruri, isolation: <br />Boot @Sump, <br />NA <br />n q <br />Wait time between applying <br />pressure/vacuimVivater and <br />starting test: <br />10 minutes <br />NA <br />k� <br />u L] U I Lull <br />TM Wr-AITH <br />Test Start Time: <br />9:55= <br />NA <br />K I T <br />Initial Reading (111): <br />10.00" hg <br />NA <br />Test End Time: <br />11: 10arn <br />NA <br />Final Reading (RF): <br />10.00" hg <br />NA <br />Test Duration: <br />75 minutes <br />NA <br />Change in Reading (RF -R'): <br />0.007'hg <br />NA <br />Pass/Fail Tbreshold or <br />Criteria: <br />0.00" hg <br />NA <br />Test Result <br />Opass ElFail <br />E]Pass E]Fail <br />ElPass E]Fail <br />E]Pass E]Fai <br />Comments — (Include information on repairs made prior to testing, and reconiiiiended.folloiv-upforfailed tests) <br />Diesel product piping is safe suction, and was verified during testing on 8-11-2008. <br />