Laserfiche WebLink
SWRCB,January 2002 Page 2 <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: ❑ Tank Manufacturer Fx Industry Standard ❑ Professional Engineer <br /> Other (Specify) <br /> Test Method Used: F] Pressure ❑x Vacuum F Hydrostatic <br /> El Other (Specify) <br /> Test Equipment Used: Equipment Resolution: <br /> No= SOMME= nomosommommom <br /> MISS Tank# 3 SUP Tank# 1 REG Tank# 2 REG Tank# <br /> rTankCapacity: <br /> t From Testing?I Yes X No Yes x No Yes x❑No 1-1 Yes No <br /> 12, 000 12, 000 12, 000 <br /> Tank Material: DW FIBERG DW FIBERG DW FIBERG <br /> Tank Manufacturer: unknown unknown unknown <br /> Product Stored: SUPREME REGULAR REGULAR <br /> Wait time between applying <br /> pressure/vacuum/water and 5min 5min 5min <br /> starting test: <br /> Test Start Time: 11:40 11:32 --- <br /> Initial Reading(Ri): 10hg 10hg -- <br /> Test End Time: 12 :40 12:32 -- <br /> Final Reading(RF ): 10hg 10hg -- <br /> Test Duration: lhr lhr -- <br /> Change in Reading(RF-RI ): 0 0 -- <br /> Pass/Fail Threshold or Criteria: 2hg 2hg --- <br /> Was <br /> --Was sensor removed for testing? ❑Yes X N NA Yes % N NA Yes N NA Yes N NA <br /> Was sensor properly replaced and �F—]Ye XN�NA ❑YeN NA ❑Ye�N Nverified functional afer testing? X CEINA <br /> DA <br /> Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> I Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />