SWRCB,January 2002 Page q of <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By: 0 Sump Manufacturer 0 industry Standard X Professional Engineer <br /> 0 Other(Specify) <br /> Test Method Used: 0 Pressure 0 Vacuum X Hydrostatic <br /> 0 Other(Specify) <br /> Test Equipment Used:Caldwell Level Change Indicator Equipment Resolution: .002 <br /> UZZISM <br /> Sump#I Sump# Sump# Sump# <br /> Sump <br /> ump Diameter: 4391 <br /> Sump Depth: 3799 <br /> Sump Material: Fiberglass <br /> Height from Tank Top to Top of Vent 19" <br /> Highest Piping Penetration: Product 16" <br /> Height from Tank Top to Lowest 13" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Dry <br /> Portion of Sump Tested' Water Level 19" <br /> Does turbine shut down when <br /> sump sensor detects liquid(both Yes No X NA Yes No NA Yes No NA Yes No NA <br /> product and water)?. <br /> Turbine shutdown response time N/A <br /> Is system programmed for fail-safe Yes No X NA Yes No NA Yes No NA Yes No NA <br /> shutdown?* <br /> Was fail-safe verified to be Yes No X NA Yes No NA Yes No NA Yes No NA <br /> operational?* <br /> Wait time between applying water 10 Minutes <br /> and start!ng test: <br /> Test Start Time: 8:45 <br /> Initial Reading(Rj): .001 <br /> Test End Time: 9:15 <br /> Final Reading(RF): .001 <br /> Test Duration: 30 Minutes <br /> Change in Reading(RF-RO: .000 <br /> Pass/Fail Threshold or Criteria: .005130 Minutes <br /> Test Result: X Pass 0 Fail Pass 0 Fail X Pass 0 Fail 0 Pass 0 Fail <br /> Was sensor removed for testing? X Yes 0 No 0 NA Yes 0 No 0 NA Yes 0 No 0 NA 0 Yes 0 No 0 NA <br /> Was sensor properly replaced and XYes ONo [INA Yes 0 No 0 NA Yes 0 No 0 NA 0 Yes 0 No 0 NA <br /> verified functional after testing? <br /> Comments—(indude information on repairs made prior to testing, and recommended follow-up forLailed tests) <br /> No Turbin! System is not Conventional Suction, or Safe Suction. <br /> System is equipped with Swing Check Valves at Tank Piping Sump, and Electric Pump Motors, <br /> that push product, from Tank Piping Sump,to Day Tank,under pressure. <br /> If the entire depth of the sump is not tested,specify how much was tested. If the answer to M of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SVrRCB LG-160) <br />