Laserfiche WebLink
SWRCB,January 2002 Page—of <br /> 6. PIPING SUMIP TESTING <br /> Test Method Developed By: 0 Sump Manufacturer 0 Industry Standard X Professional Engineer <br /> 0 Other(Specify) <br /> Test Method Used: 0 Pressure 0 Vacuum X Hydrostatic <br /> 0 Other(Specify) <br /> Test Equipment Used: Caldwell Systems Equipment Resolution: .005/30 min <br /> Sump#I <br /> MM777 Sump# Sump# Sump# <br /> NONE= <br /> Sump Diameter: 42" <br /> Sump Depth: 60" <br /> Sump Material: Fiberglass <br /> Height from Tank Top to Top of 24" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 27" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Dry <br /> Portion of Sump Tested' 2"above Highest piping penetration <br /> Does turbine shut down when <br /> sump sensor detects liquid(both 0 Yes 0 No 0 NA DYes ONo [INA OYes DNo DNA 0 Yes 0 No 0 NA <br /> product and water)?' <br /> Turbine shutdown response time <br /> Is system programmed for fail-safe El Yes 0 No 0 NA OYes ONo DNA DYes ONoDNA 0 Yes 0 No 0 NA <br /> shutdown?* <br /> Was fail-safe verified to be 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and starting 5 min 5 min 5 min 5 min <br /> test: <br /> Test Start Time: <br /> Initial Reading(R,): .0017 .001, .001, .0011 <br /> Test End Time: <br /> Final Reading(RF): <br /> Test Duration: 30 min 30 min 30 min 30 min <br /> Change in Reading(RF-Ri): <br /> Pass/Fail Threshold or Criteria: .005/30 min .005/30 min .005/30 min .005/30 min <br /> Test Result: 0 Pass x Fail 0 Pass 0 Fail 0 Pass 0 Fail 0 Pass 0 Fail <br /> Was sensor removed for testing? x Yes 0 No 0 NA xYes ONo, DNA xYes DNoDNA 0 Yes 0 No 0 NA <br /> Was sensor property replaced and x Yes No 0 NA x Yes 0 No 0 NA 0 Yes 0 No 0 NA <br /> verified functional after testipL. I I I <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Sump will not hold water. Pipe penetrations cut off at sump wall <br /> If the entire depth of the sump is not tested,specify how much was tested- If the answer to OX of the questions indicated with an <br /> asterisk(*)is"NO"or"NK',the entire sump must be tested. (See SWRCB LG-160) <br />