M <br /> 1 <br /> Chevron Monitoring Certification Checklist <br /> Store Number: 201383 Address: 1960 W.11TH STREET aQ CORRAL HOLLOW TRACY,CA 95376 <br /> Date:2/1S/2013 Technician: Steven Willems Company:YANKNOLOGYINC. <br /> Tank 1-SUPREME Tank 2-PLUS Tank 3-REGULAR <br /> Product 1 1 3 <br /> Tank Type Fiberglass Fiberglass Fiberglass <br /> (DW FRP,DW Steel,SW FRP) <br /> Tank Diameter 92.00 92.00 92.00 <br /> Annular Riser Height(measured) 64.50 64.00 65.00 <br /> Required(calculated)annular sensor length <br /> FRP tanks see Note 1 below 144.44 144.44 144.44 <br /> Steel tanks-see Note 2 <br /> Is req'd annular sensor length marked with tape& <br /> labeled with dimension Y Y Y <br /> (Y/N,document w/photo)? <br /> Actual(measured)annular sensor length 221.00 225.00 216.00 <br /> (to marked point) <br /> Are the DW pipe boots pulled back in tank sumps? <br /> (YIN or N/A,note if can't be verified because clamshell is Y Y Y <br /> pointing down) <br /> Are tank sump sensors back in their holders and in the <br /> correct position? Y Y Y <br /> (YIN or N/A document with photo) <br /> (Y/N) Comments <br /> Has the Veeder Root Battery been replaced prior to failsafe? Y <br /> Has Veeder Root Programming before&after testing been verified? Y <br /> (especially tank manifolding setup-see Note 3) <br /> Has Veeder Root Programming before&after testing been attached to the Y <br /> Work Order? <br /> Are gasoline spin on-filters replaced during testing for ethanol per <br /> Chevron requirements n/a <br /> (Cim Tek 300MB-10 or 400MB-10 or PetroCiear 40510-A only) <br /> Have all alarms generated during testing been noted in the station Alarm Y <br /> Log?(YIN) <br /> Additional Comments: <br /> Note 1: e t <br /> o <br /> N 2: <br /> DW FRP Tank Annular Calculations DW Steel Tank Annular Calculation <br /> (circumference) <br /> X=tank diameter+Riser Height <br /> X=(3.14 x tank diam/2)+riser height <br /> 10'diameter X=188"+riser <br /> &'diameter X=151"+riser <br /> 6'diameter X=113"+riser <br /> Note 3:Certain Veeder Root Software versions will automatically revert to the default tank manifold settings anytime the programming is changed,such as when <br /> sensors are temporarily X'ed out,etc <br />