Laserfiche WebLink
6 0 <br /> The following is an itemized list of underground storage tank violations that have not <br /> been addressed for RAMOS OIL-FRENCH CAMP as of December 28, 2016. <br /> Open violations from October 29, 2015 inspection <br /> Violation #210 - Designated operator monthly inspection reports not maintained on site for at least 12 <br /> months. <br /> The November 2014 and June 2015 designated operator monthly inspection reports were not found on site. The <br /> report found in the June 2015 position was dated both 6/1/15 and 7/30/15, and the attached alarm history was dated <br /> 7/1/15. Designated operator monthly inspection reports for the previous twelve months shall be retained on site. <br /> Locate and ensure that copies of the previous twelve months of designated operator monthly inspection reports are <br /> maintained on site. Submit copies to the EHD. <br /> Violation #211 - Designated operator employee training not performed or log not kept. <br /> The designated operator employee training was not performed in 2015. The last date of training was 3/19/2014. <br /> The designated operator shall train facility employees for which he or she is responsible in the proper operation and <br /> maintenance of the UST system once every 12 months. The training shall include, but is not limited to: <br /> 1. Operation of the UST system in a manner consistent with the facility's best management practices <br /> 2. Employee's role with regard to monitoring equipment as specified in the facility's monitoring plan <br /> 3. Employee's role with regard to spills and overfills as specified in the facility's response plan <br /> 4. Name of the contact person(s) for emergencies and monitoring equipment alarms <br /> Ensure that employees have been trained by the designated operator, maintain the list on site, and submit a copy of <br /> the training records to the EHD. <br /> Violation #314- Primary containment not tight(pre-Jul 2003). <br /> Diesel liquid was discovered in the UDC at 1-2, 2S-3S, 3-4, and 4S-5S dispensers, indicating a leak in the primary <br /> piping. All primary containment for the UST system must be tight. Immediately have a properly licensed, trained, <br /> and certified contractor repair or replace the failed component under permit and inspection of the EHD. <br /> Open violations from October 30, 2014 inspection <br /> Violation#103 -Current financial responsibility documents not submitted. <br /> Last financial responsibility documents submitted to the EHD and uploaded to the CERS website were dated <br /> 3/22/2013 and therefore is no longer current. Current financial responsibility documents are required to be <br /> submitted annually. Immediately log into the California Environmental Reporting System (CERS) at <br /> http://cers.calepa.ca.gov/, upload the required documents. This is a repeat violation, Class ll. <br /> Page 5 of 5 <br />