Monitoring System Certification <br /> D. Results of Testing/Servicing <br /> Software Version Installed. 8.01 <br /> Complete the following checklist: <br /> ® Yes ❑ No* Is the audible alarm operational? <br /> ® Yes ❑ No* Is the visual alarm operational? <br /> ® Yes ❑ No* Were all sensors visually inspected,functionally tested,and confirmed operational? <br /> ® Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will <br /> not interfere with their proper operation? <br /> ❑ Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) <br /> M N/A operational? <br /> 0 Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment <br /> ❑ N/A monitoring system detects a leak, fails to operate,or is electrically disconnected? If yes: which sensors initiate <br /> positive shut-down? (Check all that apply) 0 Sump/Trench Sensors; ❑Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks and sensor failure/disconnection? 0 Yes; ❑No. <br /> ❑ Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no <br /> 19 N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank <br /> fill point(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? Flap m% <br /> 0 Yes* ❑ No Was any monitoring equipment replaced? If yes,identify specific sensors,probes,or other equipment replaced <br /> and list the manufacturer name and model for all replacement parts in Section E,below. <br /> ❑ Yes* 1Z No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br /> ❑Product; ❑Water. If yes,describe causes in Section E,below. <br /> Z Yes ❑ No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable <br /> 0 Yes I Lj No* Is all monjj9dU 2guipmento perational per manufacturer's Mecifications? <br /> *In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: <br /> .Site has no external audible overfill alarm <br /> *Site tubes have overfill prevention valves <br /> *87 & 91 Mechanical leak detectors were replaced <br /> *All annular space sensors were not sitting at bottom of tank during inspection-Placed <br /> sensors at bottom of tank. <br /> *T3: Diesel 2 West has another STP sump (11/2 H.P turbine) for the low flow dispensers <br /> and has a single float V/R 794380-208 <br /> *Site has a Gilbarco dispenser that is not in use and is next to the high flow dispenser <br /> #17/18 (truck dispenser island)-The Gilbarco gasoline dispenser not in use in#'q + <br /> Page 4 of & <br />