Laserfiche WebLink
C - WATER TESTING SUMP / FITTINGS <br />It is recommended that all piping and conduits be <br />connected at this time. Clear all debris & materials from <br />the transition sump. All field installed penetration fittings <br />must be water -leak tested. <br />CA- To test field installed fittings, add enough backfill under the Transition Sump so its weight is <br />completely supported. Do not allow island supports to hold all the weight. The box will become <br />extremely heavy. <br />C.2- Fill the box with water to 2 inches above the highest fitting. After 3 hours, make a visual <br />inspection of the exterior of the box. If there are no leaks, proceed to remove the water with an <br />appropriate pump. DO NOT DRILL A DRAIN HOLE, and plan to patch the hole. <br />If there ARE leaks, proceed to Step D (below) for repair instructions. <br />D - IF ANY LEAKS ARE FOUND! ! <br />A: Locate leak point(s) and mark with marker so you can locate it / monitor it. <br />B: Repair or reinstall penetration fittings according to your penetration fitting manufacturers' <br />Installation / Maintenance Instructions. <br />C: Occasionally... Bravo Fiberglass Series Products may suffer mild damage in transit or field installation. <br />Please take a close look at edges and corners. <br />D: FOR FIBERGLASS REPAIRS: Abrade a 3" diameter area centered on the leak point until flow coat <br />is gone and natural resin/fiberglass material can be seen. Dust with shop brush or compressed air and do <br />not use shop towels or acetone. S. Bravo Systems recommends "Smith Fibercast Adhesive Kit #8014" <br />to repair and reinforce Bravo Fiberglass products. Make sure area is completely dry and apply resin <br />generously. For anything larger than pinhole leaks you must consult the factory. <br />FOR PENETRATION FITTING LEAKS/REPAIRS: Follow penetration fitting manufacturers repair <br />recommendations in their respective Installation Instructions. DO NOT compromise Bravo Product Integrity. <br />E: Let cure for a minimum of 2 hours @ or above 75° Fahrenheit. <br />4 ii -B500/600 -SW -08B <br />