Laserfiche WebLink
SWRCB,January 2002 Page 2 <br /> ` 4. TANK ANNULAR TESTING <br /> Test Method Developed By: ❑ Tank Manufacturer Industry Standard F� Professional Engineer <br /> Other (Specify) <br /> Test Method Used: rI Pressure ❑X Vacuum Hydrostatic <br /> El Other (Specify) <br /> Test Equipment Used: gauge Equipment Resolution: .2 0" <br /> Tank# 1 SUP Tank# 2 UNL Tank# Tank# <br /> Is Tank Exempt From Testing?1 Yes X No Yes x No Yes El No Yes No <br /> Tank Capacity: 15,000 20,000 <br /> Tank Material: DW FIBERG DW FIBERG <br /> Tank Manufacturer: unknown unknown <br /> Product Stored: SUPREME UNLEADED <br /> Wait time between applying <br /> pressure/vacuum/water and 5min 5min <br /> starting test: <br /> Test Start Time: 9:50 9:50 <br /> Initial Reading(Ri): 1011 1011 <br /> Test End Time: 10:50 10:50 <br /> Final Reading(RF ): 1011 10to <br /> Test Duration: lhr lhr <br /> Change in Reading(RF-P4 ): 0 0 <br /> Pass/Fail Threshold or Criteria: 211 211 <br /> MEN= son= <br /> Was sensor removed for testing? Yes X N NA Yes X N NA Yes N NA Yes N NA <br /> Was sensor properly replaced and ❑ ❑ [:] <br /> � ❑ <br /> verified functional after testing? Ye X N NA Ye X N NA Ye N NA Ye[]NcDNA <br /> Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 1 Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />