Laserfiche WebLink
SWRCB, January 2002 <br />is <br />EC' Z015 <br />Page of <br />9. SPILL/OVERFILL CONTAINMENT BOXES <br />Facility is Not Equipped With Spill/Overfill Containment BoxesEl <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: <br />❑ Spill Bucket Manufacturer <br />❑✓ Industry Standard El Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: <br />❑ Pressure <br />❑ vacuum ❑ Hydrostatic <br />[D Other (Spec) 1 hour visual leak test <br />Test Equipment Used: See attached testing procedures <br />Equipment Resolution: <br />Other <br />Spill Box # 87 Fill Spill Box # 91 Fill <br />Spill Box # 87 Vapor <br />Spill Box # 91 Vapor <br />Bucket Diameter: <br />12" 12" <br />12" <br />12" <br />Bucket Depth: <br />14 1/2" 14 1/2" <br />16" <br />16" <br />Wait time between applying <br />pressure/vacuum/water and <br />15 minutes 15 minutes <br />15 minutes <br />15 minutes <br />starting test: <br />Test Start Time: <br />9:34am 9:34am <br />9:34am <br />9:34am <br />Initial Reading (RI): <br />12 7/8" Other 11 1/2" <br />Other <br />13 3/4" Other <br />13 1/2" Other <br />Test End Time: <br />10:34am 10:34am <br />10:34am <br />10:34am <br />Final Reading (RF): <br />12 7/8" Other 11 1/2" <br />Other <br />13 3/4" Other <br />131/2 Other <br />Test Duration: <br />1 hr 1 hr <br />1 hr <br />1hr <br />Change in Reading (RF -RI): <br />0 0 <br />0 <br />0 <br />Pass/Fail Threshold or <br />0 0 <br />0 <br />0 <br />Criteria: <br />Test Result: <br />❑✓ Pass ❑Fail ❑✓ Pass <br />[]Fail <br />I ❑✓ Pass ❑Fail <br />RIPass ❑Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Direct Bury <br />