Laserfiche WebLink
R E C i <br />Q;3M <br />e <br />9. SPILL/OVERFILL CONTAINMENT BOXES JUL 2 9 2013 <br />Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ -2T <br />Test Method Developed By: <br />❑ Spill Bucket Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: <br />❑ Pressure ❑ Vacuum ❑ Hydrostatic <br />® Other (Specify) 1 hour visual leak test <br />Test Equipment Used: See attached testing procedures Equipment Resolution: <br />Bucket Diameter & Brand: <br />Spill Box # 87 fill Spill Box # 91 fill Spill Box # Spill Box # <br />12" Philtite 12" Philtite <br />Bucket Depth: <br />14.5" 14.5" <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />30 Minutes 30 Minutes 30 Minutes 30 Minutes <br />Test Start Time: <br />9:00am 9:00am <br />Initial Reading (R,): <br />12'/" 12 %" <br />Test End Time: <br />10:00am 10:00am <br />Final Reading (RF): <br />12 %1' 12 '/4" <br />Test Duration: <br />1 hour 1 hour <br />Change in Reading (RF -R,): <br />0 0 <br />Pass/Fail Threshold or <br />Criteria: <br />0.002 0.002 0.002 0.002 <br />fest ResultPass <br />Fail'ass ] fail Pass„Feel ❑ PaSS ate <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />