Laserfiche WebLink
Page 3 of 3 <br />9. SPILL/OVERFILL CONTAINMENT BOXES <br />Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: <br />❑ Spill Bucket Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: <br />❑ Pressure ❑ Vacuum ® Hydrostatic <br />® Other (Specify) I hour visual leak test <br />Test Equipment Used: See attached testing procedures Equipment Resolution: <br />Spill Box # 87 fill Spill Box # 91 fill Spill Box # Spill Box # <br />Bucket Diame7Brand:12" <br />Philtite 12" Philtite <br />epth14.5" <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />30 Minutes 30 Minutes <br />Test Start Time: <br />10:44am 9:30am <br />Initial Reading (RI): <br />4.6504 10 5/8" <br />Test End Time: <br />10:59am 10:30am <br />Final Reading (RF): <br />4.6512 10 5/8" <br />Test Duration: <br />15 min 1 hour <br />Change in Reading (RF-Rl): <br />0.00082 0 <br />Pass/Fail Threshold or 0.002 0.002 0.002 0.002 <br />Criteria: <br />,.Xh <br />tx�kA4hF <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Repairs made pursuant to Permit #SR0065794 <br />