SWRCB, January 2002 <br />0 <br />6. P SUMP TESTING <br />0 <br />Page — <br />of <br />Test Method Developed By: <br />0 Sump Manuhicturm <br />11 Other (Spec#y) <br />0 Industry Standard X Professional Engineer <br />Test Method Used. <br />0 Pressure <br />0 Other (pgw#y) <br />11 Vacuunt <br />X Hydwstatic <br />Test Equipment Used: Caldwell Systems <br />IME3311mmosom— <br />Sump # 1 <br />Sump # 2 <br />Equipment Resolution: .005/30 min <br />21affamma =� <br />Sump # 3 Sump # <br />M <br />Sump Diameter. <br />46" <br />40 <br />469 <br />Sump Depth: <br />54" <br />55" <br />5r <br />Sump Material: <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />22" <br />I r <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />29" <br />30" <br />25" <br />Condition. of sump prior W testing: <br />Dry <br />Diry <br />Dry <br />Portion of Sump Tested" <br />2" above <br />Highest piping <br />penetration <br />Does turbine shut down when <br />sump sensor detects liquid (both <br />product: and water)?* <br />x Yes 0 No 0 NA <br />xYes ONo DNA <br />xYes ONo <br />DNA <br />0 Yes 0 No <br />0 NA <br />Turbine shutdown response time <br />Is system programmed for fail-safe <br />I ?* <br />shutdown. <br />x Yes 0 No 0 NA <br />x Yes 0 No 0 KA <br />xYes ONo <br />DNA <br />0 Yes 0 No <br />0 NA <br />Was fad -safe verified to be <br />operational?* <br />0 Yes x No 0 NA <br />OYes xNo OKA <br />OYes xNo <br />DNA <br />0 Yes 0 No <br />0 NA <br />Wait time between applying <br />pressure/vacuum/water and starting <br />test: <br />5 min <br />5 min <br />5 min <br />5 min <br />Test Start Time: <br />9:50 <br />1030 <br />11:15 <br />Initial Reading (10: <br />.00" <br />.00" <br />.00" <br />.00" <br />Test End Time-, <br />10:20 <br />11:00 <br />11-45 <br />Final Reading (RF): <br />.00 <br />.00 <br />.00 <br />Test Duration: <br />30 min <br />30 min <br />30 min <br />30 min <br />Change in Reading (RF-Rj): <br />.00 <br />-00 <br />-00 <br />Pass/Fail Tbreshold or Criteria: <br />.005/30 min <br />.005/30 min <br />.005130Inmi <br />.005/30 min <br />Test Result <br />x 0 Fait <br />x Pass 0 Fag <br />x Pass 0 Fail <br />0 ftu 0 Fad <br />Was sensor removed for testing? <br />x Yes 0 No 0 NA <br />xYes ONo DNA <br />x Yes o No <br />o NA <br />0 Yes 0 No <br />0 NA <br />Was sensor properly replaced and <br />verified functional after Le�. x Yes 11 No 0 NA xYes ONo DNA x Yes o No <br />Comments — (include information on repairs made prior to tesung; and recommended follow-upfor <br />o NA 0 Yes 0 No <br />failed tests) <br />0 NA <br />' If the entire depth of the sump is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk (*) is "NO" or "NN', the entire sump must be tested. (See SWRCB LG -160) <br />