Laserfiche WebLink
INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br /> â–ºTanknobgy <br /> TEST DATE:05/24/05 8501 N MOPAC EXPRESSWAY,SUITE 400 WORK ORDER NUMBER2236535 <br /> CLIENT:CHEVRON PRODUCTS AUSTIN,TEXAS 78759(512)451-6334 SITE:CHEVRON 209167 <br /> Tank ID: #2 2 Tank manifolded: NO Bottom to top fill in inches: 117.0 <br /> Product: UNLEADED Vent manifolded: YES Bottom to grade in inches: <br /> Capacity in gallons: 19,703 Vapor recovery manifolded: YES Fill pipe length in inches: <br /> Diameter in inches: 117.00 Overfill protection: YES Fill pipe diameter in inches: <br /> Length in inches: 427 Overspill protection: YES Stage I vapor recovery: DUAL <br /> Material: DW FIBERG Installed: ATG Stage 11 vapor recovery: BALANCE <br /> CP installed on: <br /> COMMENTS <br /> Start(in) End(in) <br /> Dipped Water Level: New/passed Failed/replaced New/passed Failed/replaced <br /> Dipped Product Level: L.D.#1 L.D.#1 L.D.#2 L.D.#2 <br /> Probe Water Level: Make: VEEDERROOT <br /> Ingress Detected: Water Bubble Ullage Model: ELECTRONIC <br /> Test time: S/N: 116165 <br /> Inclinometer reading: Open time in sec: <br /> Holding psi: 21 <br /> VacuTect Test Type: NOT Resiliency cc: NOT <br /> VacuTect Probe Entry Point: TESTED TESTED <br /> Test leak rate ml/m: 189.0 <br /> Pressure Set Point: Metering psi: <br /> Tank water level in inches: Calib.leak in gph: 3.00 <br /> Water table depth in inches: Results: PASS <br /> Determined by(method): <br /> Result: <br /> COMMENTS <br /> COMMENTS <br /> Material: DW FIBERG <br /> Diameter(in): 2.0 <br /> Length (ft): 300.0 <br /> Test psi: <br /> Bleedback cc: <br /> Test time(min): NOT NOT NOT NOT <br /> Start time: TESTED TESTED TESTED TESTED <br /> End time: <br /> Final gph: <br /> Result: <br /> Pump type: PRESSURE <br /> Pump make: FE PETRO <br /> COMMENTS Impact Valves Operational: YES <br /> Printed 06/01/2005 09:56 <br />