Laserfiche WebLink
7. UNDER-DISPENSER CONTAINMENT(UDC)TESTING <br /> Test Method Developed By: ❑UDC Manufacturer p Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: See attached testing procedures Equipment Resolution: Inches <br /> UDC# 1/2 UDC# 3/4 UDC# 5/6 UDC# 7/8 <br /> UDC Manufacturer: <br /> UDC Material: Fiberglass Fiberglass Fiberglass Fiberglass <br /> UDC Depth: 32" 32" 32" 32" <br /> Height from UDC Bottom to Top 10" 10" 10" 10" <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 5" 5" 5" 5" <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to <br /> Fair Fair Fair Fair <br /> testing: <br /> Portion of UDC Tested' 4"Above highest penetration 4"Above highest penetration 4"Above highest penetration 4"Above highest penetration <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both N/A N/A N/A N/A <br /> product and water)?* <br /> Turbine shutdown response time N/A N/A N/A N/A <br /> Is system programmed for fail- ❑Yes ❑No p NA ❑Yes ❑No p NA ❑Yes ❑No p NA ❑Yes ❑No p NA <br /> safe shutdown?* <br /> Was fail-safe verified to be ❑Yes ❑No p NA ❑Yes ❑No p NA ❑Yes ❑No p NA ❑Yes ❑No p NA <br /> o erationalf <br /> Wait time between applying <br /> pressure/vacuum/water and 15 minutes 15 minutes 15 minutes 15 minutes <br /> starting test <br /> Test Start Time: 11:46am 116am: 11:25am 11:25am <br /> Initial Reading(Rj): 2.49498 Inches 0.92914 Inches 1.15888 Inches 3.27332 Inches <br /> Test End Time: 12:01 pm 12:01 pm 11:40am 11:40am <br /> Final Reading(RF): 2.49485 Inches 0.92901 Inches 1.15917 Inches 3.27329 Inches <br /> Test Duration: 15 mins 15 mins 15 mins 15 mins <br /> Change in Reading(RF-R,): 0.00013 0.00013 0.00029 0.00003 <br /> Pass/Fail Threshold or Criteria: 0.002 0.002 0.002 0.002 <br /> Test Result: _ D Piss ; Cp Fail ® Pass ❑Fail p Pass ❑Fail p'Pass: ®Fail <br /> Was sensor removed for testing? ®Yes ❑No ❑NA ®Yes ❑No ❑NA p Yes ❑No ❑NA ✓❑Yes ❑No ❑NA <br /> Was sensor properly replaced and ©Yes ❑No ❑NA ®Yes ❑No ❑NA p Yes ❑No ❑NA ®Yes ❑No ❑NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ltl li I t` <br /> 1 0NN 4''\L HE A LT H <br />