My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
ARCHIVED REPORTS_XR0007451 CASE 1
Environmental Health - Public
>
EHD Program Facility Records by Street Name
>
T
>
TURNER
>
2000
>
3500 - Local Oversight Program
>
PR0545768
>
ARCHIVED REPORTS_XR0007451 CASE 1
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
10/8/2020 10:12:41 PM
Creation date
6/9/2020 10:26:10 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
3500 - Local Oversight Program
File Section
ARCHIVED REPORTS
FileName_PostFix
XR0007451 CASE 1
RECORD_ID
PR0545768
PE
3528
FACILITY_ID
FA0003881
FACILITY_NAME
GENERAL MILLS
STREET_NUMBER
2000
Direction
W
STREET_NAME
TURNER
STREET_TYPE
RD
City
LODI
Zip
95242
APN
02903013
CURRENT_STATUS
02
SITE_LOCATION
2000 W TURNER RD
P_LOCATION
02
P_DISTRICT
004
QC Status
Approved
Scanner
LSauers
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
40
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
kq K L E l N F E L D E R <br /> 3 BACKGROUND <br />' General Mills operates a food production facility located at 2000 West Turner Road in Lodi, <br /> California The facility includes an office, fuel storage areas, silos, parking areas, etc , for food <br /> production purposes <br />' Kleinfelder reviewed pertinent documents and information related to the USTs on the site provided <br /> by General Mills Based on Klernfelder's review of this information, Kleinfelder understands the <br />' UST area discussed in this report is located south of the office and approximately 10 feet north of <br /> Building No 86 (See Plate 1) The two USTs were oriented north to south and situated side by <br /> side on an approximate 30 foot by 30-foot reinforced concrete pad At one time, the two 10,000- <br /> gallon USTs reportedly contained diesel, kerosene and/or JP-4 jet fuel <br />' According to a PHS/EHD inspection report, a single 10,000-gallon fiberglass UST was removed <br /> from the site on January 29, 1988 Apparently the tank was removed due to an unauthorized <br /> release The tank removed was shown as being the easternmost tank of two USTs Iocated side by <br />' side and north of a "new" building The bottom of the tank was at a depth of approximately 12 <br /> feet bgs and located on a large concrete pad Two bottom soil samples were taken at each end of <br /> the tank, at the ends of the concrete pad, at approximately 14 feet bgs <br /> Kleinfelder reviewed analytical data reports associated with these two samples conducted by <br /> California Water Labs Inc , dated January 29, 1988 The two soil samples were analyzed for <br />' total petroleum hydrocarbons as referenced to gasoline (TPH-G) diesel (TPH-D), kerosene (TPH- <br /> K) and motor oil (TPH-MO) and benzene, toluene and xylenes (BTX) The northernmost soil <br /> sample was reported by the laboratory as "none detected" for the requested analyses at or above <br /> laboratory reporting limits TPH-K was the only analyte detected at 19 0 mg/kg from the soil <br /> sample collected from the southern end of the tank <br />' An unauthorized release report was prepared by county employee William R Snavely, dated <br /> January 14, 1988 This report indicated that a leak was discovered due to inventory discrepancy <br />' and that approximately 123 gallons of JP1 Fuel was involved Comments in this report stated the <br /> following "Manager discovered a discrepancy in inventory and called ITT Tank Service to check <br /> system, leak in filler pipe observed, Stockton Service Station advised that the tank be removed, <br /> tank is being pumped out and to be empty 1/12/88 " <br /> The remaining UST is positioned on the western half of the pad As part of Kleinfelder's initial <br />' investigation, borings were advanced to assess the soil conditions as they pertain to possible soil <br /> contamination, due to operations of the existing UST (western side of cement pad) pnor to its <br /> proposed abandonment in place <br /> The General Mills facility utilized flus UST and the previously removed UST for fuels used to run <br /> the turbines in their production process Klelnfelder understands that currently there is only one <br />' 18748 T02/ST02R795 Page 3 of 1 1 <br /> ©2002 Kleinfelder,Inc December 3,2002 <br />
The URL can be used to link to this page
Your browser does not support the video tag.