Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for DIAMOND GAS AND FOOD MART as of May11, 2020 . <br /> Open violations from June 04 , 2019 inspection <br /> Violation #306 - Monitoring equipment is not installed or maintained to detect a leak at the earliest <br /> opportunity. <br /> The UCD 7/8 , and UDC 3 /4 sump sensor was raised approximately 2-3 inches off the lowest point of the sump and <br /> not located to detect a leak at the earliest opportunity. Liquid was observed in UDC 7/8 as well as a leaky 91 product <br /> meter. Monitoring equipment shall be maintained to be able to detect a leak at the earliest possible opportunity. The <br /> sensor was relocated to the lowest point of the sump by the service technician . Ensure that all monitoring <br /> equipment is maintained to detect a leak at the earliest opportunity. <br /> ❑ This violation was corrected ❑ This violation will be corrected by (date) : <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation : <br /> Violation #313 - Failure to construct, operate , and maintain primary containment as product-tight. <br /> In UDC 7/8 , 91 product fuel meter was observed to leaking , indicating a leak in the primary piping . All primary <br /> containment for the UST system must be tight. Immediately have a properly licensed , trained , and certified <br /> contractor repair or replace the failed component under permit and inspection of the EHD . <br /> ❑ This violation was corrected ❑ This violation will be corrected by (date) : <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation : <br /> Page 4 of 4 <br />