Laserfiche WebLink
S A N J D AR I N Environmental Health Department <br /> Y AMENDED <br /> 11/16/2020 <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Marks Fuel& Food, Inc. 880 E VICTOR RD, LODI September 29, 2020 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 208 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> OBSERVATION: The designated operator inspections for the following months were performed more than 30 days <br /> after the previous inspection: <br /> - Initial inspection on 1/24/2020, next inspection performed on 3/16/2020(52 days) <br /> REGULATION GUIDANCE: The designated operator visual inspections shall be conducted within 30 days or less of <br /> the previous inspection. <br /> CORRECTIVE ACTION: Ensure that all designated operator inspections are performed within the required time <br /> frames. <br /> OBSERVATION: The designated operator failed to check and note the correct test dates for the secondary <br /> containment testing and overfill testing on designated operator inspection reports. <br /> -Overfill was listed as 7/31/2019 but it was performed on 1/11/2019. <br /> -Secondary containment was listed as 12/4/2019 but was performed on 9/11/2019. <br /> REGULATION GUIDANCE: During the inspection, the designated operator shall check that all required testing and <br /> maintenance for the UST system have been completed and document the dates they were done. <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of <br /> the required information on the reports. <br /> OBSERVATION: Designated operator reports were not signed by the owner/operator within the required time frame. <br /> REGULATORY GUIDANCE:Within 48 hours of the completion of the designated UST operator visual inspection, <br /> the designated operator shall sign and provide the owner or operator with a copy of the inspection report. Within 72 <br /> hours of being provided a signed copy of the report,the owner or operator shall provide a description of each <br /> corrective action taken or to be taken and shall sign and date the report, acknowledging the identified compliance <br /> issues. <br /> CORRECTIVE ACTION: Ensure all designated operator inspection reports are completed and signed within the <br /> required time frame in the future. <br /> This is a repeat violation, Class ll. <br /> FA0003862 PR0231746 SCO01 09/29/2020 <br /> EHD 23-01 Rev.9/16/2020 Page 5 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />