Laserfiche WebLink
as <br /> EITT <br /> April 12, 1988 <br /> TEST DATA & RESULTS <br /> Page 1 <br /> Mara Ann Manser <br /> SUNNYSIDG PRODUCE <br /> P. 0. Box 433 Site: 8960 W. Walnut Grove Road <br /> Thornton, California 95686 Thornton, California . <br /> Dear Ms , Manser: <br /> The following is a summary of the precision testing we recently <br /> conducted on your underground storage ank (s) . <br /> E.�c-Iosed are copies of the test w rksheets n <br /> .during ��the testing. The are and graphs generated <br /> arrpriate Y Provide for your submittal to t"he <br /> govenmental agency. <br /> A tank system is considered tight, according to the <br /> current <br /> regulations, if -the gain_ is less than .02 or the loss is less than .05 <br /> gallons per one hour of testing. If the results shown below are <br /> beyond these parameters, you will need to take 'remedial actio'. <br /> Please note page .2 of this letter if a o is shown in the final column <br /> below. U <br /> TANK # TANK PRODUCT TEST WITHIN "TIGHT" <br /> LOCAT101i CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> South 10, 300 U/L Gas -. 16527 No <br /> Please contact us if you need additional assistance or <br /> intarmatj.un. I� <br /> i� <br /> Sincerely, <br /> W'. Savage 'a <br /> Cert Pied Tester <br /> i <br /> ©Ow2l� $3'1,86; <br />