Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for GRANT LINE SHELL* as of May 12 , 2020 . <br /> Open violations from May 30, 2019 inspection <br /> Violation #201 - Failure to maintain monitoring , maintenance , and follow up action records . <br /> Secondary containment results for the test conducted on 5/24/ 18 , 7/5/ 18 , 7/6/ 18 and 7/ 12/18 were not found on <br /> site . These results shall be maintained on site for at least three years . Monitoring records include : ( 1 ) date and time <br /> of all monitoring or sampling ; (2 ) monitoring equipment calibration and maintenance records ; (3 ) results of any <br /> visual observations ; (4) results of sample analysis performed a lab or in the field ; (5 ) logs of all readings of gauges <br /> or other monitoring equipment , ground water elevations , or other test results ; (6 ) results of inventory readings and <br /> reconciliations . Immediately locate and maintain all secondary containment results for the last three years on site <br /> and submit copies to the EHD . <br /> ❑ This violation was corrected 11This violation will be corrected by (date) . <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation : <br /> Violation #202 - Failure to maintain the " Facility Employee Training Certificate" on-site ( after October 1 , <br /> 2018 ) . <br /> On the 4/ 10/19 and 11 /21 / 19 no Designated operator name was provided . On the 4/ 10/ 19 Justin Alejandrino , and <br /> Tony Villalobos were trained on 2/ 15/ 19 and the date of assuming responsibility was 2/ 13/ 19 , two days before they <br /> were trained . Furthermore , the DO is listing employees in the training forms for which training has been previously <br /> provided to in other dates repeatedly. Ensure that the training log is used only for the employees that are train on the <br /> date of the training . All site employees must be trained prior to taking responsibility as a facility employee if after <br /> October 1 , 2018 , or within 30 days of hire if prior to October 1 , 2018 . The " Facility Employee Training Certificate" <br /> shall contain accurate information for all employees trained . Update the " Facility Employee Training Certificate" to <br /> contain the accurate information and submit a copy of the updated form to the EHD . <br /> ❑ This violation was corrected ❑ This violation will be corrected by ( date) . <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation : <br /> Violation #204 - Current monitoring plan approved by the EHD not found on site . <br /> An approved copy of the monitoring plans were not available for inspection . A copy of these plans shall be <br /> accessible on site at all times . Immediately locate and retain a copy on site . Monitoring plan found on site was <br /> outdated and incorrect . <br /> Page 2 of 5 <br />