Laserfiche WebLink
14. ( Tanks subject to floatation [Section 2635 (a) (7)] • <br /> • t( A. Anchored by deadman or slab. <br /> of B. Anchors to be installed as specified by manufacturer. <br /> �C C. Installation details provided on plans. i7A-Cw" <br /> D. Calculations provided. j (� <br /> 17. SPILL AND OVERFILL PREVENTION <br /> OC Underground storage tank equipped with spill container and an overfill prevention system. (detail drawing of spill <br /> containers)/piping sump(s) required, including tank fill and all openings). <br /> OC A. Spill container [Section 2635 (b) (1)]. <br /> If made of metal, exterior wall protected from galvanic corrosion. <br /> of Capacity: (minimum of five gallons) tjg:21lvn <br /> N Equipped with a drain valve which allows drainage of spilt into primary container. <br /> OC Manufacturer:- Forme-G'o <br /> OC B. Overfill prevention system does not allow for manual override and meets one of the following requirements: <br /> (1) Alert transfer operator at 90% full by restricting the flow into the tank or triggering an audible <br /> and visual alarm [Section'1{2..6355((b)(2)(A)] . <br /> Manufacturer: eme o W�tl°dyn Model: 1100 <br /> (2) Restrict delivery flow to the tank 30 minutes before overfill when tank is filled at no more than <br /> 95% capacity and activates an audible alarm at Least five minutes before overfill [Section 2635 <br /> (b) (2) (B)]. <br /> Manufacturer: Model: <br /> (3) Provide positive shut off at no more than 95% capacity [Section 2635 (b) (2) (C)]. <br /> Manufacturer: Model: <br /> (4) Provide positive shut-off of flow to the tank so that the fittings on top of the tank are not <br /> exposed to the product overfilling [Section 2635 (b) (2) (D)]. <br /> Manufacturer: Model: <br /> 18. PIPING INFORMATION (primsr'1/Ser. Product <br /> PIPING INFORMATION TANK# TANK# OZ TANK# TANK# <br /> DISTANCE from <br /> DISPENSER to TANK <br /> MANUFACTURER To+a1 GDfitalhrnerr <br /> SYSTEM TYPE re, <br /> CONSTRUCTION '* poow'e' Wall <br /> MATERIAL *** f:1exib1e, 1'101'1 -Me4zIIG �Et"1�IItD�1-eX, <br /> LEAK DETECTION SYSTEM tidel eirilb b 4zm , line 1r3k cL-tei:+on <br /> 100% METHANOL COMPATIBILITY YES NO <br /> CORROSION PROTECTION YES NO <br /> * System Type; suction, pressure, and gravity <br /> ** Construction: single-walled, double-walled, Lined-trench, etc. <br /> *** Material Type; steel with cathodic protection, stainless-steel, fiberglass reinforced plastic. <br /> 7 <br />