hlb jnmj Says & Waig—
<br />Diameter
<br />Capacity
<br />Length
<br />Weight
<br />36"
<br />150
<br />2'-10"
<br />184
<br />36"
<br />285
<br />5'-4"
<br />287
<br />48"
<br />550
<br />6'0"
<br />555
<br />48"
<br />1000
<br />10'-9"
<br />1,385
<br />64"
<br />1000
<br />6'-0"
<br />1,263
<br />64"
<br />1500
<br />9'-0"
<br />1,679
<br />64"
<br />2000
<br />12'-0"
<br />2,101
<br />64"
<br />3000
<br />18'-0"
<br />2,936
<br />64"
<br />4000
<br />24'-0"
<br />3,747
<br />76"
<br />2000
<br />9'-0"
<br />2,198
<br />76"
<br />3000
<br />13'-4"
<br />3,245
<br />Diameter
<br />Capacity
<br />Length
<br />'Weight
<br />76"
<br />4000
<br />16'-10"
<br />3689
<br />76"
<br />5000
<br />22'-2"
<br />5,012
<br />96"
<br />5000
<br />14'-0"
<br />5,056
<br />96"
<br />6000
<br />16'-1"
<br />5,633
<br />96"
<br />8000
<br />21'-4"
<br />7,061
<br />96"
<br />10000
<br />27'-0"
<br />8,603
<br />96"
<br />12000
<br />32'-0"
<br />9,941
<br />120"
<br />10000
<br />17'-2"
<br />7,722
<br />120"
<br />12000
<br />20'-6"
<br />8,846
<br />120"
<br />15000
<br />25'-8"
<br />13,079
<br />120"
<br />20000
<br />34'-1"
<br />16,560
<br />Guide Specifications—Jacketed Steel Underground Storage Tanks
<br />Short Form
<br />The contractor shall provide a Jacketed Steel Underground Storage
<br />tank consisting of structural innerwall and a semi-rigid outerwall, as
<br />shown on drawings. The primary vessel shall be a U.L labeled, steel
<br />underground storage tank and the secondary containment vessel shall
<br />be a Tank Jacket, as manufactured by Total Containment, Inc.
<br />Tanks shall be tested and installed in accordance with the manufac-
<br />turers published installation instructions and only approved bedding
<br />and backfill material may be used.
<br />Long Foram
<br />Construction
<br />Primary Storage Vessel: Shall be a steel underground storage tank,
<br />all welded construction in accordance with the requirements of UL -58
<br />and tested and labeled accordingly.
<br />Secondary Containment Vessel: At the factory, a 2 psi air pressure
<br />and soap test shall be performed to detect any pinhole leaks. An air
<br />pressure soap test, not more than 1 psi, shall be performed at the job -
<br />site, before installation. After installation, before backfilling to grade, an
<br />air pressure hold test shall be performed no greater than 2 psi.
<br />Integrity Testing
<br />Primary Storage Vessel: At the factory, a 5 psi air pressure and soap
<br />test shall be performed to detect any pinhole leaks. If required, a 5 psi
<br />air pressure hold test may be performed after installation before
<br />backfilling to grade.
<br />Secondary Containment Vessel: At the factory, a 2 psi air pressure
<br />and soap test shall be performed to detect any pinhole leaks. An air
<br />pressure soap test, not more than 1 psi, shall be performed at the job -
<br />site, before installation. After installation, before backfilling to grade, an
<br />air pressure hold test shall be performed no greater than 2 psi.
<br />Licensed Manufacturer:
<br />Construction Materials
<br />Primary Storage Vessel: Shall be a prime grade steel as required by
<br />U.L, ASME, API, N.F.P.A. 30 and U.F.C.
<br />Secondary Containment Vessel: Shall be fabricated of a high density
<br />polyethelene, 100 mils in thickness.
<br />Product Compatibility
<br />Both the primary storage vessel and the secondary containment vessel
<br />shall be compatible with gasoline, gasohol, ethanol, methanol, jet fuel,
<br />av-gas, kerosene, diesel fuel, motor oil at ambiant underground
<br />temperatures; or used for fuel oil not to exceed 150°F.
<br />Interstitial Fluid Migration
<br />There shall be an interstitial space between the primary storage. vessel
<br />and secondary containment vessel created by high density
<br />polyethelene stand-off mesh with a highilow profile to allow 100% fluid
<br />migration, under maximum loads, between the walls.
<br />Corrosion Protection
<br />The primary storage vessel (steel) shall provide striker plates under
<br />each fitting to eliminate internal impact corrosion. The secondary con-
<br />tainment vessel shall totally isolate the primary storage vessels from
<br />stray electrical currents as well as the environment. A sufficient quan-
<br />tity of hydrated lime shall be inserted within the interstitial space so as
<br />to raise the ph level to above 10.
<br />Monitoring Access
<br />The secondary containment vessel shall provide a monitoring access
<br />fitting for insertion of a continuous monitoring probe. This fitting shall
<br />be located at the lower end of the sloped tank.
<br />5�sx:i:,:, -'a..i..:!.7%n,}"+'„."t.'w'A�=zPr�:xzrs.^.wktr_a..s.o�.,.,�e+=-'�.+-a' a. ',wsti.✓".