UNDER DISPLIASER CONTAINMENT DC TESTING <br /> Test Method By: O Manufacturer 0 Industry Standard O Professional Engr O Other(see below) <br /> Test Method Uses: O Pressure O Vacuum • Hydrostatic O Other(see below) <br /> Measuring Equipment Used: INCON TS-STS (Electronic Sump Test System) <br /> Description Disp#1/2 Disp#3/4 <br /> UDC manufacturer Bravo Bravo <br /> UDC material FRP FRP <br /> UDC depth (inches) 30 30 <br /> Height from UDC bottom to highest 13 12 <br /> piping penetration <br /> Height from UDC bottom to lowest 6 7 <br /> electrical penetration <br /> Condition of UDC prior to testing Dry Dry <br /> Portion of UDC tested Entire Entire <br /> Type of shut-down present Stand Alone Stand Alone <br /> Was sensor removed for testing? Yes Yes <br /> Was sensor properly replaced after testing? Yes Yes <br /> Depth of water level from UDC bottom (in.) 16 15 <br /> Wait time for water level to stabilize (hr:min) 0:08 0:10 <br /> Test start time 9:38 AM 9:38 AM <br /> Initial Probe Reading 4.5687 3.1013 <br /> Test end time 9:53 AM 9:53 AM <br /> Final Probe Reading 4.5686 3.1013 <br /> Test duration (hr:min) 0:15 0:15 <br /> Change in water level (±0.0000 inches) -0.0001 0.0000 <br /> Pass/Fail threshold (±0.0020 inches/;Hr.) 0.0020 0.0020 <br /> TEST RESULT PASS PASS <br /> Comments: <br /> © 2004 Walton Engineering,Inc. <br />