Laserfiche WebLink
E <br />Ll <br />Test Method Developed By: 1:1 Tank Manufacturer 9 Industry Standard 11 Professional Engineer <br />Test Method Used: 0 Pressure 0 Vacuum El Hydrostatic <br />Test Equipment Used: Vacuum Gauges/Pump Equipment Resolution: <br />Tank # 87 Tank 9 J Tank Al <br />Is Tank Exempt From Testing? 0 Yes (8 No <br />Tank Capacity: 12,000 <br />Tank Material: Fiberglass <br />Tank Manufacturer: <br />Trusco, <br />i Product Stored: Unleaded 87 <br />Wait time: <br />15 min <br />Test Start Time: 9:00 <br />Initial Itial Reading (inHG) 10 <br />Test End Time: 10:00 <br />Final Reading (!nHG) 10 <br />1 -in, Duration (hh:mm): 01:00 i01:00 01:00 <br />Change in Reading (inHG): 0.0 0.0 <br />0.0 <br />Pass/Fall Threshold o`r----'---- <br />Cdteria: 0 0 <br />Test Result: *Pass 0 Fail <br />I ryas sensor removed tor I <br />testing? @Yes 0 No 0 NA <br />Was sensor properly replaced <br />and verified functional after <br />®Yes 0 N ONA <br />testing? <br />Comments: This is a post 6 -month follow up test for a repair done on the 87 primary it; June. <br />2 of 7 <br />Tank # <br />00;00 <br />0.0 <br />