Laserfiche WebLink
Page 1 of 1 <br />Garrett Backus [EH] <br />From: Garrett Backus [EH] <br />Sent: Monday, May 04, 2009 2:28 PM <br />To: 'sandy.huff@valero.com' <br />Subject: 1210 Hammer Lane, Stockton <br />Hi Sandy, <br />Alpha Petroleum and I did the cold start inspection for the EVR upgrade today. The ISD portion will be done at a <br />latter date and under a different permit. We tested the liquid sensors and overfill prevention tank gauge only. The <br />outside audio/visual alarm did not work when initially tested but the tech fixed the wiring and the alarm tested OK. <br />The site was not programmed to shut down the turbines when the liquid sensors were in alarm. If you would like <br />to keep the facility set up this way then an annual primary piping line test is required. Typically, the line test is <br />done during the monitoring system certification testing. The annual monitoring system certification will be done in <br />July as we discussed by phone a few weeks ago. <br />Garrett Backus, REHS <br />San Joaquin County Environmental Health Department <br />600 E. Main Street <br />Stockton, CA 95202 <br />telephone: (209) 468-2986 <br />fax: (209) 468-3433 <br />email: gbackus@sjcehd.com <br />5/4/2009 <br />