• 4 <br /> 0 <br /> Triangle Environmental, Inc. <br /> 2525 West Burbank Blvd.,Burbank,CA 91505-2302 <br /> (818)840-7020 (818)840-6929 <br /> UST TESTING SYSTEMS S'UM A R Y SHEE T <br /> Precision Underground Storage Tank System Leak Test <br /> Client: <br /> Phillips 66 Company Phillips Facility # 05447 <br /> 1500 North Priest Drive <br /> Tempe, AZ 85281 Test ate: 7/ 1/02 <br /> Kathy Strickland <br /> (602)728-7149 <br /> Facility: 2705447 Work#: 12901032 <br /> Phillips Facility#05447 County: SAN JOAQUIN <br /> 1469 E HAMMER LN Cross Street: E HAMMER LANE/WEST LANE <br /> STOCKTON, CA 95209 <br /> Tank Test System Tank Line <br /> # Product Capacity Type Rate/Results Ullage Result Rate/Result L/D Result <br /> 1 Unleaded Regular 12068 N/A N/A 0.000 PASS PASS <br /> 2 Unleaded Premium 10583 N/A N/A 0.000 PASS PASS <br /> 3 Unleaded Plus 10583 N/A N/A -0.005 PASS PASS <br /> 4 Diesel 10583 N/A N/A 0.000 PASS PASS <br /> Certified By: Technician: Tom Corcoran State Lic.#s: <br /> Mfgr's#: TEI-067 <br /> Comments: <br /> Compliance P-L/TST, monitor certification&Grounding. Stage II A/L. <br /> This precision tank testing system has been third party evaluated according to the guidelines of the EPA <br /> procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0.10 <br /> gph with a Pd>95%and Pfa<5%as required by Local,State and Federal EPA UST Technical <br /> Standards Part 280 for precision testing systems. This SB-989 secondary containment testing system <br /> exceeds the criteria for detection as required by state and local agencies. <br />