Laserfiche WebLink
a t <br /> Triangle Environmental, Inc. <br /> SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility Phillips Facility <br /> Tank TI : 1 est Date: / 1/02 <br /> Product: Unleaded Regular Work#: 12901032 <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: 12068 Manufacturer: Red Jacket <br /> Diameter(in): L/D Model: FX <br /> Product Level(in): L/D Serial#: <br /> Liquid Volume(Gals): Line Drain Back(ml): 140 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 28 <br /> Coef of Expansion: Metering Pressure(psi): 10 <br /> Water On Tank(in): L/D Test Rate(gph): 3.0 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): <br /> Test Start Time: <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(gph): Pump Brand: Red Jacket <br /> Test Result: N/A System Type: Pressure <br /> Line Pressure(psi): 50 <br /> Line Start Time: 12:30:00 PM <br /> Test Method: ULLAGE Line End Time: 12:45:00 PM <br /> UllageVolume(gals.): Line Start Level: 210 <br /> Ullage Test Time: Line End Level: 210 <br /> Ullage Vacuum(psi): Line Test Rate(gph): 0.000 <br /> Ullage Result: N/A Line Test Result: PASS <br /> 2 <br />