Laserfiche WebLink
Triangle Environmental, Inc. <br /> SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Phillips Facility <br /> Tank #: 3 Test Date: 7/ 1/02 <br /> Product: Unleaded Plus Work#: 12901032 <br /> NEEMEM <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: 10583 Manufacturer: Red Jacket <br /> Diameter(in): L/D Model: FX <br /> Product Level(in): L/D Serial#: <br /> Liquid Volume(Gals): Line Drain Back(ml): 120 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 26 <br /> Coef.of Expansion: Metering Pressure(psi): 10 <br /> Water On Tank(in): L/D Test Rate(gph): 2.9 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): <br /> Test Start Time: <br /> Test Method: TEI LT-3 <br /> Test End Time: <br /> Test Rate(gph): Pump Brand: Red Jacket <br /> Test Result: N/A System Type: Pressure <br /> Line Pressure(psi): 50 <br /> Line Start Time: 12:30:00 PM <br /> Test Method: ULLAGE Line End Time: 12:45:00 PM <br /> UllageVolume(gals.): Line Start Level: 180 <br /> Line End Level: 175 <br /> Ullage Test Time: <br /> Ullage Vacuum(psi): Line Test Rate(gph): -0.005 <br /> Ullage Result: N/A Line Test Result: PASS <br /> 3 <br />