Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: ARCO #00548 <br /> Tank : 1 Test ate: 2/ 5/97 <br /> Product: Unleaded Regular Work#: 340281 <br /> Test Method: System 4000 Test Method: R.J.FTA <br /> Capacity: 10000 Manufacturer: Red Jacket <br /> Diameter(in): 91 L/D Model: FX-l V <br /> Product Level(in): 71 L/D Serial#: 091196-5401 <br /> Liquid Volume(Gals): 7800 Line Drain Back(ml): 110 <br /> Liquid Percent(%): 78.0% L/D Trip Time(sec): 2 <br /> Specific Gravity: 0.750 Holding Pressure(psi): 15 <br /> Coef.of Expansion: 0.000660 Metering Pressure(psi): 11 <br /> Water On Tank(in): 0 L/D Test Rate(gph): 1.3 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): 60 <br /> Head Pressure(psi): 1.9 MENEM= <br /> Test Start Time: 8:30:00 AM Test Method: TEI LT-3 <br /> Test End Time: 11:00:00 AM Pump Brand: Red Jacket <br /> Test Rate(gph): -0.034 <br /> System Type: Pressure <br /> Test Result: PASS Line Pressure(psi): 50 <br /> Line Start Time: 12:20:00 PM <br /> Test Method: ULLAGE Line End Time: 12:35:00 PM <br /> UllageVolume(gals.): 2200 Line Start Level: - 330 <br /> Ullage Test Time: 11:30:00 AM Line End Level: 300 <br /> Ullage Vacuum(psi): 1 Line Test Rate(gph): -0.03 <br /> Ullage Result: PASS Line Test Result: PASS <br /> 2 <br />