Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: CO #00548 <br /> Tank : 2 Test Date: 2/ 5/97 <br /> Product: Unleaded Premium Work#: 340281 <br /> Test Method: System 4000 Test Method: R.J.FTA <br /> Capacity: 6000 Manufacturer: Vaporless <br /> Diameter(in): 94 L/D Model: LD2000 <br /> Product Level(in): 84 L/D Serial#: 35643 <br /> Liquid Volume(Gals): 5300 Line Drain Back(ml): 60 <br /> Liquid Percent(%): 88.3% L/D Trip Time(sec): 2 <br /> Specific Gravity: 0.750 Holding Pressure(psi): 24 <br /> Coef,of Expansion: 0.000660 Metering Pressure(psi): 10 <br /> Water On Tank(in): 0 L/D Test Rate(gph): 0.8 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): 64 <br /> Head Pressure(psi): 2.3 <br /> Test Start Time: 8:30:00 AM Test Method: TEI LT-3 <br /> Test End Time: 11:00:00 AM pump Brand: Red Jacket <br /> Test Rate(gph): -0.04 System Type: Pressure <br /> Test Result: PASS Line Pressure(psi): 50 <br /> Line Start Time: 12:40:OA PM <br /> Test Method: ULLAGE Line End Time: 12:55:00 PM <br /> UllageVolume(gals.): 700 Line Start Level: 260 <br /> Ullage Test Time: 11:40:00 AM <br /> Line End Level: 240 <br /> Ullage Vacuum(psi): 1 Line Test Rate(gph): -0.02 <br /> Ullage Result: PASS Line Test Result: PASS <br /> 3 <br />