Laserfiche WebLink
WESTERN AMERICA TANK TESTING, INC. <br /> 3131 Fairhaven Drive <br /> Bakersfield, CA 93308 <br /> (805) 322-9827 <br /> ANNUAL 3 -STEP RED .JACKET LEAK DETECTOR TEST <br /> OWNER QUIK STOP MARKET <br /> LOCATION Stor_ktoni CA. #120 DATE August 3 , 1.989 <br /> PRODUCT : Regular, Unleaded, � Premium Unleaded,' Diesel (Cirele one) <br /> NOTE : Use separate form for each Tank . <br /> ( 1 ) Running Pressure 25 ( `Z ) Shut-Off Pressure 14 <br /> ( 3) Amount of Product Released thru Bibcock to Zero 4 oz . <br /> (4) With Valve Open-- --Start STP - List-, Pressure - ,-- - -23 P. S . T . , <br /> (5 ) Reduce Flow to Rate of 7 oz . per Minute - List Pressure at. this Flow <br /> Rate 22 _ _ _ _1'. S . I . , <br /> (6) Turn STP Off - Let. Pressure drop to zero thru Leak just created - List <br /> time for Gauge to Reach Zero 1 min. _ — sec. , <br /> (7 ) Turn the STP back on - Keep Leak Rate at Bibcock - List pressure <br /> 24 F. S . I . - Flow Rate at Nozzle . 50 G . P.M. , <br /> (8) Stop Leak with STP still on - Does Leak Detector reset X yes __no <br /> If yes - How long to reset min 3 sec. , <br /> (9) Turn STP off -- List. pressure 2 _ P. S . I . , <br /> ( 10) Turn STP brick on -- List time to reach pressure rise __min . 25 sec. <br /> ( 11 ) List Pressure 24 lP. S . I . , <br /> ( 12) Open Nozzle and List Pressure 24 P. S . T . <br /> SATISFACTORY LEAK DETECTOR X Yes No. <br /> LEAK DETECTOR <br /> Model Red Jacket. ___ ____�, Date Code &. Serial <br />