Laserfiche WebLink
I � <br /> WESTERN AMERICA TANK TESTING, INC. <br /> 3131 Fairhaven Drive <br /> Bakersfield, CA 93308 <br /> (805) 322-9827 <br /> ANNUAL 3-STEP RED JACKET LEAK DETECTOR TEST <br /> OWNER QUIK STOP MARKET <br /> LOCATION Stockton , CA. #120 DATE August 3_, 1989 <br /> PRODUCT: Regular, ('-Unleaded,-"-) Premium Unleaded, Diesel. (Circle one) <br /> NOTE : Use separate form for each Tank. <br /> ( l. ) Running Pressure _ 25 (2) Shut-Off Pressure__- 0 , <br /> ( 3) Amount of Product Released thru Bibcock to Zero 0 oz . <br /> (4) With Valve Open--Start. STP - List Pressure 8 P. S . I . , <br /> ( 5) Reduce Flow to Rate of 7 oz . per Minute - List Pressure at this Flow <br /> Rate 12 _ P. S . I . , <br /> (6) Turn STP Off - Let: Pressure: drop to zero thru Leak just created - List <br /> time for Gauge to Reach Zero min . 25 sec. , <br /> (7) Turn the STP back on - Keep Leak Rate at Bibcock - List pressure <br /> 12 P. S . I . - Flow Rate at Nozzle — . 50 G. P.M. , <br /> (8) Stop Leak with STP still on - Does Leak Detector reset X yes no <br /> If yes - How long to reset — min 3 sec. , <br /> (9) Turn STP off - L:ist pressure 0 P. S . I . , <br /> ( 10) Turn STP back on - List time to reach pressure rise mina 5 sec. <br /> ( 11 ) List Pressure 25 _P. S . I . , <br /> ( 12) Open Nozzle and List Pressure 25 P. S . I . <br /> SATISFACTORY LEAK DATECTOR X Yes Nom. <br /> LEAK DETECTOR <br /> Model Red Jacket _, Data Code & Serial. # <br />