Laserfiche WebLink
WESTERN AMERICA TANK TESTING, INC. <br /> 3131 Fairhaven Drive <br /> -' Bakersfield, CA 93308 <br /> (805) 322-9827 <br /> ANNUAL 3-STEP RED JACKET LEAK DETECTOR TEST r <br /> OWNER QUIK STOP MARKET <br /> LOCATION — Stockton . CA. #120 DATE August 3, 1989 <br /> PRODUCT: Regular, Unleaded, Premium Unleaded, Die elm (Circle one) <br /> NOTE : Use separate form for each Tank. <br /> ( 1 ) Running Pressure_,_ 25 �� (2) Shut.-Off Pressure 2 , <br /> (3) Amount of Product Released thru Bi.bcock to Zero 1 pz , <br /> (4) With Valve Open--Start: STP — List Pressure 12 P. S . I . , <br /> (5) Reduce Flow to Rate of 7 oz . per Minute - List Pressure at this Flow <br /> Rate 15 _ P. S . I . , <br /> (6) Turn STP Off - Let Pressure drop to zero thru Leak just. created - List <br /> time for Gauge to Reach Zero min. 20 sec.', <br /> (7) Turn the STP back on - Keep Leak Rate at Bibcock - List: pressure <br /> 12 _P. S . I . - Flow Rate at Nozzle . 50 G. P. M. , <br /> (8) Stop Leak with STP still on - Does Leak Detector reset X yes no <br /> If yes - How long to reset min 5 sec. , <br /> (9) Turn STP off -- List. pressure i 2 F. S . T . , <br /> ( 10) Turn STP back on - List time to reach pressure rise min . 25 sec. <br /> ( 11) List Pressure _ _ 25 __P. S . I . , <br /> ( 1.2) Open Nozzle and List Pressure 25 P. S . I . <br /> SATISFACTORY I,EAH__I)F`I'fs C T 0 R Y e. _ ___ _. _ No. <br /> LEAK DETECTOR <br /> Model _ Red Jacket_.__�___.._ _ , Date Codt> & Serial <br />