Laserfiche WebLink
• • <br /> WESTERN AMERICA TANK TESTING, INC. <br /> 3131 Fairhaven Drive <br /> Bakersfield, CA 93308 <br /> (805) 322-9827 r <br /> r-, <br /> ANNUAL 3--STEP RED_ JACKET LEAK DETECTOR ITST <br /> OWNER GNU T K STOP MARKET <br /> LOCATION _ Stockton,iC,A._ #120 DATE __ August--:3 . 1989 <br /> PRODUCT: (, Regular-, tin Ieaded , Premium Unleaded, Diese:! (G.ir'c1e one) <br /> �. <br /> NOTE : Use separate form for each Tank . <br /> ( 1 ) Running Pressure 25 " Shut--Off Pre-ssure 2 <br /> (3) Amount of Product Released thru Bibcock to `hero _ � OZ <br /> ( 4 ) With Valve Open---Start: STP List Pressures —_- --- ----- 12 <br /> ( 5) Reduce Flow to Rate of 7 oz . per Minute - List. Pressure at this Flow <br /> Rate 15 ---P. S . I <br /> ( 6) Turn STP Off - Let Pressure drop to zero thr•u Leak just created - List <br /> time for Gauge to Reach Zero min . 20 _ ser_ . , <br /> (7) Turn the STP back on - Keep Leak Rite at Bibcock - hast. pressure <br /> 12 P. S . I . - Flow Rate at Nozzle . 50 G. P.M. , <br /> (8) Stop Leak with STP still on - Does Leak Detector reset. X_yes no <br /> If yes -- How long to reset min b sec. , <br /> ( 9) Turn STP off' - List pressure 2 P. S . I . , <br /> ( 10) Turn STP back on --- List time to reach pressure rise min . 25 sec. <br /> ( 11 ) List Pressure: 25 _ P. S . I . , <br /> ( 1.2) Open Nozzle and List Pressure 25 <br /> SATISFACTORY LEAK DETECTOR _ X Yves <br /> LEAK DETECTOR <br /> Model Red Jacket. Date Code & <br />