Laserfiche WebLink
The following is deemed a defect for the affected fueling Point(s) ors ystem, <br /> Fueling Points <br /> 1. <br /> The fueling Point shall be removed from service when more than 30% of a <br /> seal is Missing (e.g., a triangular or similar shape in which greater then 2.5 inchnozzle face <br /> es of the <br /> faceplate circumference is Missing (accumulated)), <br /> Z The fueling Point shall be removed from service when more than 0.375 square inches of <br /> a nozzle vapor collection sleeve is Missing (e.g., a rectangular shape Of greater than <br /> nine/sixteenth (9/16) inches or more on each side, a circular shape of eleven/sixteenth <br /> {11/16) inches or more in diameter, or a <br /> the side. triangular shape of seven/eighth (7/8) inches on <br /> 3. The fueling point shall be removed from service when the total slit legth <br /> convolutions exceeds 18 inches as determined by direct measurements, in the <br /> 4. The fueling Point shall be removed from service when a hose is found <br /> than 175 ml of gasoline in the vapor side as determined by sections 6.1 to have greaterof Exhibit <br /> 5. Note: Prior to draining gasoline from the vapor side of the VST hose, use VST tool <br /> P/N VST-STP-100 and Plug the fuel spout. Do not activate dispenser when draining <br /> gasoline from the vapor side Of the VST hos,9. <br /> 5. The fueling Point shall be removed from service when VST system pressure dr <br /> exceeding the following conditions as determined by Methodology I of TP-201,4 <br /> s <br /> 5.00 inches WC at a now rate of 60 CFH of Nitrogen; and <br /> 6. &00 inches WC at a flow rate Of 80 CFH of Nitrogen. <br /> The fueling Point shall be removed from service when the dispensing rate is greater than <br /> ten 0 0) gallons per minute (gPM) or less than five (5) as determined <br /> applicable Provisions of section 6 or 7 of Exhibit 5 or by dirgpm ect observation by forthe 30 <br /> seconds minimum at the maximum hand held Position. <br /> 7. The fueling Point shall be removed from service when any hose has a visible opening s <br /> determined by direct observation, e a <br /> 8. The fueling Point shall be removed from service when the insertion interlock mechanism <br /> allows dispensing when the bellow is uncompressed as determined by direct observation <br /> 9. or GDF-09 (see Vapor Recovery Defects List). <br /> The fueling Point shall be removed from service when the nozzle automatic liquid shut- <br /> off mechanisms malfunction in any manner as determined by EPO Na. 26-F (See Vapor <br /> Recovery Defects List) or direct observation. <br /> 10. The fueling Point shall be removed from service when any nozzle has a defective vapor <br /> valve as determined by Exhibit 10 or when the vapor valve has a leak rate that exceeds <br /> VST Phase 11 EVR System, Exhibit 2-VR-203-E <br />