Laserfiche WebLink
PRODUCT PIPING SUMP TESTING <br />Test Method By: O Manufacturer • Industry Standard o Professional Engr o Other (see below) <br />Test Method Uses: O Pressure O vacuum 0 Hydrostatic o Other (see below) <br />Measuring Equipment Used: INCON TS -STS (Electronic Sump Test System) <br />Description Tank #1 Tank #2 Tank #3 <br />Tank product <br />Gasoline - 91 <br />Gasoline - 87 Master <br />Gasoline - 87 Syphon <br />Sump material <br />FRP <br />FRP <br />FRP <br />Sump diameter (inches) <br />42" <br />42" <br />42" <br />Sump depth (inches) <br />34" <br />41" <br />36" <br />Height from tank top to highest <br />piping penetration (inches) <br />9" <br />11" <br />14" <br />Height from tank top to lowest <br />electrical penetration (inches) <br />14" <br />13" <br />10" <br />Method of sump attachment to tank <br />Tank Collar <br />Tank Collar <br />Tank Collar <br />Condition of sump prior to testing <br />Dry <br />Dry <br />Dry <br />Portion of sump tested <br />Entire <br />Entire <br />Entire <br />Is system programmed for fail-safe operation? <br />Unknown <br />Unknown <br />Unknwon <br />Was fail-safe verified to be operational? <br />No <br />No <br />No <br />Was sensor removed for testing? <br />Yes <br />Yes <br />Yes <br />Was sensor properly replaced after testing? <br />Yes <br />Yes <br />Yes <br />Depth of water level from tank top (inches) <br />0 <br />17" <br />15" <br />14" <br />Wait time for water level to stabilize (hr:min) <br />0:10 <br />0:10 <br />0:10 <br />Test start time <br />8:50 AM <br />8:50 AM <br />8:50 AM <br />Initial Probe Reading <br />4.0868 <br />6.4869 <br />6.3669 <br />Test end time <br />9:05 AM <br />9:05 AM <br />9:05 AM <br />Final Probe Reading <br />4.0869 <br />6.4887 <br />6.3664 <br />Test duration (hr:min) <br />0:15 <br />0:15 <br />0:15 <br />Change in water level (t 0.0000 inches) <br />0.0001 <br />0.0018 <br />-0.0005 <br />Pass/Fail threshold (10.0020 inches /; Hr.) <br />0.0020 <br />0.0020 <br />0.0020 <br />TEST RESULT <br />PASS <br />PASS <br />PASS <br />Comments: <br />Depth of water level from tank top (inches) <br />0 <br />17" <br />15" <br />14" <br />Wait time for water level to stabilize (hr:min) <br />0:10 <br />0:10 <br />0:10 <br />Test start time <br />8:50 AM <br />8:50 AM <br />8:50 AM <br />Initial Probe Reading <br />4.0868 <br />6.4869 <br />6.3669 <br />Test end time <br />9:05 AM <br />9:05 AM <br />9:05 AM <br />Final Probe Reading <br />4.0869 <br />6.4887 <br />6.3664 <br />Test duration (hr:min) <br />0:15 <br />0:15 <br />0:15 <br />Change in water level (t 0.0000 inches) <br />0.0001 <br />0.0018 <br />-0.0005 <br />Pass/Fail threshold (10.0020 inches /; Hr.) <br />0.0020 <br />0.0020 <br />0.0020 <br />TEST RESULT <br />PASS <br />PASS <br />PASS <br />2006 Walton Engineering, Inc. <br />