Laserfiche WebLink
TANK ANNULAR TESTINGY, <br /> Test Method By • Manufacturer O Industry Standard O Professional Engr. O Other(see below) <br /> Test Method Uses: o Pressure ® Vacuum o Hydrostatic o Other(see below)' <br /> Measuring Equipment Used: Vacuum Gauge (range 0 to 30 inches Hg) <br /> Description Tank#1 Tank#2 Tank#3 <br /> Product stored Gasoline-87 Gasoline-89 Gasoline-91 <br /> Tank manufacturer Unknown Unknown Unknown <br /> Tank material FRP FRP FRP <br /> Tank capacity (US gallons) 10,000 10,000 8,000 <br /> Is this a multi-compartment tank? No No No <br /> Dry or Brine filled annular? Dry Dry Dry <br /> Monitoring system show normal annular? Yes Yes Yes <br /> Is water table above tank bottom? Unknown Unknown Unknown <br /> Was sensor removed for testing? No No No <br /> Was sensor properly replaced after testing? N/A N/A N/A <br /> Wait time for vacuum to stabilize (hr:min) 0:10 0:10 0:10 <br /> Test start time 11:11 AM 11:11 AM 11:11 AM <br /> Initial vacuum (inches Hg) 10.0 10.0 10.0 <br /> Test end time 1:11 PM 1:11 PM 1:11 PM <br /> Final vacuum (inches Hg) 10.0 10.0 10.0 <br /> Test duration (hr.min) 2:00 2:00 2:00 <br /> Change in vacuum (inches Hg) 0.0 0.0 0.0 <br /> Pass/Fail threshold (inches Hg/hour) 2.0 2.0 2.0 <br /> TEST RESULT PASS PASS PASS <br /> Comments: <br /> Tanks 1,2,3 are manifolded together with one vent risor. <br /> The gauge on tank#1 was used to record the results. <br /> 0 2016 Walton Engineering,Inc. <br />