Laserfiche WebLink
This section describes the hardware, requirements, and procedures for installing the Solid -State Discriminating <br />Containment Sump, Discriminating Containment Sump, and Solid -State Containment Sump Sensors. <br />Installation Hardware <br />All Discriminating Containment Sump Sensors come with the following installation hardware: <br />• One 12 -Foot Long Cable (including connector) <br />If a longer cable is required, you may order a 20 foot long cable (for either 2 -wire or 3 -wire sensors) separately. <br />For 2 -wire sensors, order Part No. 331102-001; for 3 -wire sensors, order Part No. 331103-001. <br />• 1 Wiring Kit <br />• 1 Installation Instructions <br />• Mounting brackets are required and must be ordered separately. Use of Veeder-Root Universal Mounting Kit <br />(Part No. 330020-012) is recommended. <br />Table 2. Containment Sump Installation Hardware Part Numbers <br />Sensor <br />Cable Part No. <br />Wiring Kit Part No. <br />Solid -State Discriminating <br />331103-002 <br />330020-011 <br />Containment Sump <br />Discriminating Containment <br />331102-002 <br />330020-011 <br />Sump <br />Solid -State Containment <br />331102-002 <br />330020-011 <br />Sump <br />Installation Requirements <br />Before you install each Containment Sump Sensor, consider the following important requirements: <br />1. The sensor should rest in the cup or lowest point of the containment sump. <br />2. It is recommended that the sensor be mounted in a true vertical position to ensure proper operation of the <br />sensor. <br />3. The sensor must be positioned as close to the containment sump outer wall as possible. <br />8 <br />